Connect to your meter#

Get an optical probe#

The simplest way to start reading data from your meter is via the optical port. You will need an optical probe to read the data, like these ones.

There are many makes of probes. Usually each meter manufacturer also sells a variant, but they can be a bit pricey, however they are usually of good quality.

Is your meter using direct HDLC or IEC62056-21 Mode E handshake?#

This library, as of now, just supports the direct HDLC enabled meters.

When you have a meter using IEC62045-21 you need to start with an IEC62056-21 initiation sequence before you can start the HDLC session. Meters have it this way to enable users to still read the meter via the optical port using the simpler IEC62056-21 protocol. Check out our python library for IEC62056-21

Find out how to address your meter.#

When using HDLC you will need to know the physical address to use in HDLC communications. This is not something that is standardized, and you might have to try different values to get it to work.

Here are some values we have gathered:

Manufacturer Meter client physical address server (meter) physical address
Iskraemeco AM550 1 17

Is your meter protected?#

Most meters have at least two association options. You can connect to the public part via the public_client of the meter to read non sensitive data but for reading current and historical values you will need to use the management client

These addresses are reffered as logical addresses. A meter can have several logical devices in one physical meter (mostly its just one) so the server_logical_address is to address which logical device in the meter you want to connect to and the client_logical_address shows with what kind of client privileges you want to connect with.

The public client uses client_logical_address=16 and the management client uses client_logical_address=1.

Other addresses can be used for clients with specific privileges or for pre-established associations. This is up the meter manufacturer and/or the companion standard the meter supports to define.

Password#

A meter can use no security, Low Level Security (LLS) or High Level Security for the authenticating against the meter

No security means that no password needs to be submitted.

Low Level Security just means a password needs to be submitted.

High level security involves several passes with exchange of challenges between the client and meter and then verifying those challenges. Several methods of validating the challenge exists.

  • Manufacturer specific
  • MD5
  • SHA1
  • GMAC
  • SHA256
  • ECDSA

As of now dlms-cosem supports HLS-GMAC

Encryption and authentication#

Your meter might enforce encryption and/or authentication of messages. If you don't have the keys it will be impossible to communicate with your meter.

Each encryption key also have an invocation counter. This is to protect the meter from replay attacks. After each use the invocation counter needs to be incremented. If the meter receives a message with an invocation counter that is the same or lower than in the last message it will discard the message.

If you don't know the current invocation counter you can usually read it from the meter using the public client.

It is also possible to sign messages and use a public key infrastructure for encryption, but it is not yet supported in dlms-cosem

Security Suite#

A meter also usually adheres to a security suite (0-2). All this does is defining what cryptographic functions should be used for certain cryptographic operations.

Operation Security Suite 0 Security Suite 1 Security Suite 2
Authenticated Encryption AES-GCM-128 AES-GCM-128 AES-GCM-256
Key Transport AES-GCM-128 AES-GCM-128 AES-GCM-256
Digital Signature NA ECDSA with P-256 ECDSA with P-384
Key Agreement NA ECDSA with P-256 ECDSA with P-384
Hash NA SHA-256 SHA-384
Compression NA v.44 v.44

For now the most important take away from the security suite is to make sure you are using keys of the correct length.

Simple example#

from dlms_cosem.client import DlmsClient
from dlms_cosem import cosem, enumerations

usb_port: str = "/dev/tty.usbserial-A704H991"

# public client
dlms_client = DlmsClient.with_serial_hdlc_transport(serial_port=usb_port,
                                                    server_logical_address=1,
                                                    server_physical_address=17,
                                                    client_logical_address=16, )

# Send HDLC connection and send an ApplicationAssociationRequest (AARQ)
dlms_client.associate()

# read an invocation counter
data: bytes = dlms_client.get(
    cosem.CosemAttribute(interface=enumerations.CosemInterface.DATA,
                         instance=cosem.Obis(0, 0, 0x2B, 1, 0), attribute=2, ))

# Release the association by sending a ReleaseRequest and then closing the HDLC connection
dlms_client.release_association()

# alternatively use the contextmanager .session() to handle the association and
# connection automatically.
with dlms_client.session() as client:
    data: bytes = client.get(
        cosem.CosemAttribute(interface=enumerations.CosemInterface.DATA,
                             instance=cosem.Obis(0, 0, 0x2B, 1, 0), attribute=2, ))